25103, EPR-PVC (15000V Grounded, Shielded) Type MV90 Power Cable- 100 % Insulation Level, 1/0 Get a Quote Today

Construction

Conductor

  • Annealed copper conductor.

Insulation

  • Extruded conductor shield, EPR ethylene propylene rubber insulation, extruded insulation shield, No. 22 AWG metallic wire shielding or copper shielding tape.

Jacket

  • Black polyvinyl chloride jacket, surface printed.

Application

  • As medium voltage MV-90 power cable for use in main feeder, distribution and branch circuits in industrial, commercial and electric utility installations. Cables may be used in wet or dry locations in circuits not exceeding 15000 volts 100% insulation level, at conductor temperatures not exceeding 90°C for normal, 130°C for emergency overload and 250°C for short circuit conditions. Suitable for installation in conduit, tray, trough, ducts, aerial and direct burial applications.

Approvals

  • Conforms to AEIC CS6 for ethylene propylene rubber Insulated shielded power cables,
  • Conforms to ICEA pub. no.S-68-516 and NEMA pub. no. WC8 for ethylene-propylene-rubber-insulated wire and cable.
  • Listed by UL as Type MV-90, per standard 1072.
  • Listed by UL as sunlight resistant.
  • Sizes 1/0 and larger UL listed for CT use.
  • Conforms to federal specification J-C-30B.


AttributeValue
Item #25103
Item NameEPR-PVC (15000V Grounded, Shielded) Type MV90 Power Cable- 100 % Insulation Level
Size (AWG/MCM)1/0
Strands19
Nominal O.D (inches)1.100
Current-Tray (Amps)-
Current-Conduit (Amps)195
Current-Duct (Amps)200
Nominal Weight(LBS/MFT)715