15057, Building Wire- Type THHN or THHN PVC with Nylon Jacket, 600V, 8 Get a Quote Today
Construction
Conductor:
- Annealed uncoated copper conductor, PVC insulation, nylon jacket, surface printed.
Applications:
- General purpose wiring in accordance with the NEC, maximum conductor temperature of 90°C in dry locations and 75°C in wet locations, 600 volts, for installation in conduit or other recognized raceway.
- Also used for wiring of machine tools (stranded), appliances, and control circuits not exceeding 600 volts.
Industry Approvals:
- Listed by UL as type THHN or THWN per Standard 83, and as Type MTW per Standard 1063 (stranded items).
- Listed by UL as Gasoline and Oil Resistant II.
- Listed by UL as sunlight resistant (1/0 AWG and larger, black only).
- 1/0 AWG and larger pass UL and IEEE-383 ribbon burner flame test and are listed for CT use.
- Listed by UL as 105°C appliance wiring material, 80°C where exposed to oil.
- Conforms to Federal Specification J-C-30B.
Note:
As THHN:90°C conductor temperature and 30°C ambient in dry locations.
As THWN:75°C conductor temperature and 30°C ambient in wet or dry locations.
Attribute | Value |
---|---|
Item # | 15057 |
Item Name | Building Wire- Type THHN or THHN PVC with Nylon Jacket, 600V |
Size (AWG/MCM) | 8 |
Strands | 19 |
Current- 75°C (amps) | 50 |
Current- 90°C (amps) | 55 |
Nominal Weight(LBS/MFT) | 71 |
Insulation Type | MTW, THWN or THHN |