Supplier Of Electrical Wire & Cable | Custom Wire and Cable  
  











  




  



















  
      


  
    





Request For Quote

13104, XHHW Power Cable- 3 Conductor With Ground - Type TC - NEC® ARTICLE 340 - 90°C Wet & Dry- 600V, 1 Get a Quote Today

Construction

Conductor

  • Class B stranded uncoated copper conductor.

InsulationXLP crosslinked polyethylene insulation, surface print phase identification (black and numbered).

Cabling

  • Three insulated conductors twisted with a class B stranded uncoated copper grounding conductor and suitable fillers, cable tape.

Jacket

  • Black PVC jacket overall, surface printed.

Applications

  • As flame-retardant three conductor power cables rated 600 volts, 90° C in wet or dry locations. Specifically approved for installation in cable trays per Article 340 of the NEC. Type TC cables are approved for use in Class I and II, Division 2 hazardous locations. Cables may be installed in open air, in ducts or conduits, in tray or trough, or direct buried.

Approvals

  • Listed by UL as type TC tray cable per Article 340 of the NEC.
  • Individual conductors UL listed as type XHHW-2.
  • Overall jacket UL listed as sunlight resistant.
  • Cables pass UL and IEEE- 383 ribbon burner flame tests.
  • Cables UL listed for direct burial.
  • Cables meet requirements of ICEA pub. no. S-66-524 and NEMA pub. no. WC7 for crosslinked polyethylene insulated wire and cable.


AttributeValue
Item #13104
Item NameXHHW Power Cable- 3 Conductor With Ground - Type TC - NEC® ARTICLE 340 - 90°C Wet & Dry- 600V
Size (AWG/MCM)1
Strands19
Nominal O.D (inches)1.130
Ground Wire Size AWG6
Current at 75° C (Amps)130
Current at 90° C (Amps)150
Nominal Weight(LBS/MFT)1170