13121, XHHW Power Cable- 4 Conductor With Ground - Type TC - NEC® ARTICLE 340 - 90°C Wet & Dry- 600V, 6 Get a Quote Today

Construction
Conductor
- Class B stranded uncoated copper conductor.
Insulation
- XLP crosslinked polyethylene insulation, surface print phase identification (black and numbered).
Cabling
- Four insulated conductors twisted with a class B stranded uncoated copper grounding conductor in two opposite valleys, suitable fillers, cable tape.
Jacket
- PVC jacket overall, surface printed.
Application
- As flame-retardant four conductor power cables rated 600 volts, 90° C in wet or dry locations. Specifically approved for installation in cable trays per Article 340 of the NEC. Type TC cables are approved for use in Class I and II, Division 2 hazardous locations. Cables may be installed in open air, in ducts or conduits, in tray or trough, or direct buried.
Approvals
- Listed by UL as type TC tray cable per Article 340 of the NEC.
- Individual conductors UL listed as type XHHW-2.
- Overall jacket UL listed as sunlight resistant.
- Cables pass UL and IEEE- 383 ribbon burner flame tests.
- Cables UL listed for direct burial.
- Cables meet requirements of ICEA pub. no. S-66-524 and NEMA pub. no. WC7 for crosslinked polyethylene insulated wire and cable.
Attribute | Value |
---|---|
Item # | 13121 |
Item Name | XHHW Power Cable- 4 Conductor With Ground - Type TC - NEC® ARTICLE 340 - 90°C Wet & Dry- 600V |
Size (AWG/MCM) | 6 |
Strands | 7 |
Ground Wire Size AWG | 10 |
Current at 90° C- Direct Burial (Amps) | 60 |
Current at 75° C- Direct Burial (Amps) | 52 |
Current at 90° C Tray (Amps) | 75 |
Current at 75° C Tray (Amps) | 65 |
Nominal Weight(LBS/MFT) | 575 |